1.Specification
16 photo-coupler isolated digit input with SOE and Counter
2 ports ,RS485 or RS232( 3 wire) ,
Modbus RTU
2.Parameters
Digit Input
16 Channel Digit Input, Photo-coupler Isolated, Dry contacts
Commons: all Negative
DC 12v~48V Input Voltage :
20kΩ Input resistance
SOE with 1ms resolving
Pulse Counter with 32BIT
1KHz Maximum Counter Frequency
Communication
2, RS485 or RS232( 3 wire) , Modbus RTU
Max baud rate 38400bps
Address Setting: DIP SW 1~31
3.Operation Condition
Operating temperature: -20°C~ 70°C
Storage temperature: -40~85°C
Operating humidity: <85% RH(20±5°C)
atmospheric: 86~108Kpa, No corrosive gas or heavy dust
Weight: 450g
Input/Output M3 screw terminals
Mounting: Surface or DIN rail
Size: 125×110×40 mm
Power Supply: AC 85~265V 40HZ~65HZ or DC 24 v OR DC12V
Power Consumption: < 3W
Ingress Protection: IP30
Application & Certification